Closed Tank DP Type Level Measurement with Dry leg and transmitter installed below tapping point
https://instrumentationtools.blogspot.com/2015/04/Closed-Tank-DP-Type-Level-Measurement-with-Dry-leg-and-transmitter-installed-below-tapping-point.html
Closed Tank Level Measurement with Dry leg and Transmitter installed below Tapping Point
DP LEVEL TRANSMITTER DRY LEG CALIBRATION |
This calculation used for closed tank level measurement with Dry leg type calibration
The formulas for calculating transmitter URV and LRV are as follows:
HP Side or LRV or Transmitter 0% = X.S
LP Side or URV or Transmitter 100% = S(X+H)
Where
S = Specific gravity of tank liquid or process liquid.
H = Tank Height
X = Distance between transmitter and HP tapping point.
NOTE:
1. The Parameters H,X can be entered in any units like mmh20, inh20 but must be same