Density Measurement using DP Transmitter for closed tank with wet leg

In closed tanks, the DP transmitter must compensate for the pressure of the vessel above the liquid surface. So the LP side of transmitter is connected to the tank. Here in this post we are discussing about calibration of DP transmitter for a closed tank with wet leg & constant level application for density measurement. This is only used for constant level application.
Density Measurement using DP Transmitter for closed tank with wet leg
Density Measurement using DP Transmitter for closed tank with wet leg

The minimum and maximum process specific gravities can be obtained from process datasheets.



The formulas for calculating the tranmitter LRV and URV are;

HP Side/LRV/4ma = L.Smin - H.Sref

LP Side/URV/20ma = L.Smax - H.Sref

Where
L = Closed tank maximum measured level
H = Height of wet leg
Smax = Maximum process specific gravity
Smin = Minimum process specific gravity
Sref = wet leg or reference leg specific gravity


Note: This calculation is only used for closed tank with wet leg and for constant level application.

Related

Convert Percentage (0-100)% to current (4-20)ma

Convert % to ma Percentage to Current Conversion tool: This is used to convert the percentage 0 - 100 % to standard current signal (ma) in the range of 4 - 20 ma. . This calculation tool use...

RTD Calculator : Calculate temperature from resistance

RTD Calculator RTD Conversion tool: This is used to calculate temperature value of RTD sensor from known resistance. . This calculation tool used to find out the temperature value of a RTD se...

RTD Calculator : Calculate Resistance from temperature

RTD Calculator RTD Conversion tool: This is used to calculate resistance value of RTD sensor from known temperature. . This calculation tool used to find out the resistance value of a RTD se...

Post a Comment Default Comments

emo-but-icon
:noprob:
:smile:
:shy:
:trope:
:sneered:
:happy:
:escort:
:rapt:
:love:
:heart:
:angry:
:hate:
:sad:
:sigh:
:disappointed:
:cry:
:fear:
:surprise:
:unbelieve:
:shit:
:like:
:dislike:
:clap:
:cuff:
:fist:
:ok:
:file:
:link:
:place:
:contact:

PopularRecentComments

Recent

Free PLC Training Courses and Tutorials

Free PLC training courses and articles to learn Programmable Logic Controllers with example ladder logic programs.Free PLC Training CoursesFree Siemens PLC CourseFree Wincc SCADA CourseFree Allen Brad...

PLC Study Material

PLC Study Material, PLC Theory, PLC Logic, PLC Interview Questions and Answers, PLC Ladder Logic, PLC Example Programs, Programmable Logic Controllers Study Materials. PLC S...

Magnetic Flow Meters Working Animation

Magnetic Flow Meters Working Animation Simply, Magnetic Flow Meters works on Faraday's Law of ElectroMagnetic Induction. The Two Green dots in the animation indicates electrodes. The Copper co...

Electromagnetic Flow Meters Working Principle

Magnetic flow meter, simply known as mag flow meter is a volumetric flow meter which is ideally used for wastewater applications and other applications that experience low pressure drop and with app...

Control Valve Selection Guide

Control valves play a major role in the everyday effort to increase process plant profitability and conserve energy. Proper selection of these valves can have a significant financial impact on the o...

Comments

JOHN MULINDI:

This is a good explanation that is very helpful to students aspiring to pursue instrumentation at university or collage level.

بلال:

Thank you very much for the information

Anonymous:

is there any laser sensor[transmitter or switch ] and is it suitable for industrial use , if it is suitable what is the advantage and disadvantages comparing to ultrasonic or radar , thanks a lot for ...

Anonymous:

for controlling [start/stop] of pump which is the suitable ,radar or ultrasonic?
I am planning to use non contact switch

Instrumentation Android App

item