Closed tank DP Level Transmitter with wet leg Zero elevation Calibration

Schematic Diagram of a Closed tank DP Level Transmitter with wet leg Zero elevation Calibration

Closed tank DP Level Transmitter with wet leg Zero elevation Calibration

Formulas: 
Min range = - SG . H 
Max range = - SG . (H-X)

You can use our instrumentation tools for easy & online calculation of transmitter ranges.CLICK HERE.

Example:

If the height of an X is 2 meters and height H is 2.5 meters, there is fluid in the tank which has a density of 1 g / cm3, what is the range of calibration on the Trasmitter? 


SG = 1
Min range = - 1 x (2.5 - 0)
= - 1 x 2,5 m
= - 2.5 mH 2 O

Max range = -1 X (2.5 - 2)
= -1 X 0.5 m
= -0.5 MH 2 O

The Transmitter Range = -2.5 to -0.5 mH 2 O