Industrial Instruments Questions and answers

1. What are the process Variable? 

The process Variable are: 1) Flow 2) Pressure 3) Temperature 4) Level 5) Quality i. e. % D2, C02, PH etc. 

2. Define all the process Variable and state their unit of measurement. ? 

1) FLOW: Kg I hr, Litter I min, Gallon I min. M3 I NM3 I HR. (GASES) 

2) PRESSURE: Force acting per unit Area. P = F/A Units: Bar I Pascals I Kg I CM I, Pounds 

3) LEVEL: Different between two heights. Units: Meters, M M, C M, %. 

4) TEMPERATURE: It is the degree of hotness or coldness of a body. Units : Degree Centigrade, Degree Farenheit, Degree Kelvin, Degree Rankin. 
Instruments Questions and answers
Instruments Questions and answers

5) QUALITY: It deals with analysis PH, % C02, % 02, Conductivity, Viscosity. 

3. What are the primary elements usedfor flow measurement. ? 

The primary elements used for flow measurement are: 1) Orifice Plate. 
2) Venturi tube. 
3) Pitot tube. 
4) Annubars. 
5) Flow Nozzle. 
6) Weir & Flumes. 

4. What are the differnt types of orifice plates and state their uses? 

The different types of orifice plates are: 
1) Concentric. 
2) Segmental. 
3) Eccentric. 

CONCENTRIC: The concentric orifice plate is used for ideal liquid as well as gases and steam service. This orifice as a hole in concentric and hence known as concentric orifice. 

Eccentric & Segmental: The accentric orifice plate has a hole eccentric. The use this is made in viscous and sherry flow measurement. 

The segmental orifice place has the hole in the form segment of a circle. This is used for colloidal and sherry flow measurement. 

Also Read:Flow Measurement Interview Questions & Answers

5. How do you identify an orifice in the pipe line. ? 

An orifice tab is welded on the orifice plate which extends our of the line giving an indication of the orifice plate. 

6. Why is the orifice tab provided. ? 

The orifice tab is provided due to the following reasons. 1) Indication of an orifice plate in a line. 2) The orifice diameter is marked on it. 3) The material of the orifice plate. 4) The tag no. of the orifice plate. 5) The mark the inlet of an orifice. 

7. What is Bernoulli's theoram and where it is applicable. ? 

Bernoulli's theoram states the "total energy of a liquid flowing from one point to another remains constant." It is applicable for non compressible liquids. 

8. How do you identify the H. P. side or inlet of an orifice plate in line. ? 

The marking is always done H. P. side of the orifice tab which gives an indication of the H. P. side. 

9. How do you calibrate a D. P. transmitter. ? 

The following steps are to be taken which claribrating : 
1) Adjust zero of the Xmtrs. 
2) Static preasure test: Give equal pressure on both sides of the transmitter. Zero should not shift. If it is shifting carry out static aligntment. 
3) Vaccum test: Apply equal vaccum to both the sides. The zero should not shift. 
4) Calibration Procedure: 
 a) Give 20 psi air supply to the transmitter.
b) Vent the L.P. side to atmosphere. 
c) Connect output of the Instrument to a standard test gauge. Adjust zero. 
d) Apply required pressure to high pressure side of the transmitter and adjust the span. 
e) Adjust zero again if necessary. 

10. What is the seal liquid used for filling impulse lines on crude and viscous liquid? 

Glycol. 

11. How do you carry out piping for a Different pressure flow transmitter on liquids, Gas and steam services? Why? 

Liquid lines: On liquid lines the transmitter is mounted below the orifice plate. Since liquids have a property of self draining.

Gas Service: On gas service the transmitter is mounted above the orifice plate because Gases have a property of self venting and secondly condensate formation.

Steam Service: On steam service the transmitter is mounted below the orifice plate with condenlate pots. The pots should be at the same level.

12. An operator tells you that flow indication is more? How would you start checking?

1) First flushing the transmitter. Flush both the impulse lines. Adjust the zero by equalizing if necessary. If still the indication is more then. 
2) Check L.P. side for choke. If that is clean then. 
3) Check the leaks on L.P. side. If not. 
4) Calibrate the transmitter.

13. How do you do a zero check on a D.P. transmitter?

Close one of the valve either H.P. or L.P. open the equalizing valve. The O/P should read zero.

14. How would you do Glycol filling or fill seal liquids in seal pots 7Draw and explain.

The procedure for glycol filling is : 
1) Close the primary isolation valves. 
2) Open the vent on the seal pots. 
3) Drain the use glycol if present. 
4) Connect a hand pump on L.P. side while filling the H.P. side with glycol. 
5) Keep the equalizer valve open. 
6) Keep the L.P. side valve closed. 
7) Start pumping and fill glycol. 
8) Same reeat for L.P. side by connecting pump to H.P. side, keeping equalizer open and H.P. side isolation valve closed. 
9) Close the seal pot vent valves. 
 10) Close equalizer valve. 
 11) Open both the primary isolation valves.

15. How do you calculate new factor from new range using old factor and old range. ?

New Factor = _!New Range Old Factor = _IOld Range Flow = K_!Range

Q = Factor X Unit Flow

New Factor = Old Factor I _IOld Range X _/New Range.

16. How will you vent air in the D.P. cell? What if seal pots are used?

1) Air is vented by opening the vent plugs on a liquid service transmitter. 
2) On services where seal pots are used isolate the primary isolation valves and open the vent valves. Fill the line from the transmitter drain pluge with a pump.

13. Why is flow measured in square root?

Flow varies directly as the square root of different pressure F = K square root of AP. Since this flow varies as the square root of differential pressure the pen does not directly inlicate flow. The flow can be determinded by taking the square root of the pen. Say the pen reads 50% of chart.

Also Read: Instrumentation Interview Questions & Answers

Related

Interview Questions on Fire detection system

1.What is a ‘fire triangle’? A fire triangle represents the three elements, which causes a fire in a combustible mixture. The three elements are fuel, air and ignition.   Interview Questio...

Interview questions on Bearing temperature measurement

1.what approximately is the bearing high temperature alarm and shutdown setting? High speed bearings are protected against high temperatures. The high temperature alarm and shutdown instrument ...

Interview questions on Vibration Measurement

1.What is ‘vibration’? Vibration is defined as the motion of the equipment or its part to and from its rest (static) condition.   Interview questions on Vibration Measurement 2.Explai...

Post a Comment Default Comments

emo-but-icon
:noprob:
:smile:
:shy:
:trope:
:sneered:
:happy:
:escort:
:rapt:
:love:
:heart:
:angry:
:hate:
:sad:
:sigh:
:disappointed:
:cry:
:fear:
:surprise:
:unbelieve:
:shit:
:like:
:dislike:
:clap:
:cuff:
:fist:
:ok:
:file:
:link:
:place:
:contact:

PopularRecentComments

Recent

Free PLC Training Courses and Tutorials

Free PLC training courses and articles to learn Programmable Logic Controllers with example ladder logic programs.Free PLC Training CoursesFree Siemens PLC CourseFree Wincc SCADA CourseFree Allen Brad...

PLC Study Material

PLC Study Material, PLC Theory, PLC Logic, PLC Interview Questions and Answers, PLC Ladder Logic, PLC Example Programs, Programmable Logic Controllers Study Materials. PLC S...

Magnetic Flow Meters Working Animation

Magnetic Flow Meters Working Animation Simply, Magnetic Flow Meters works on Faraday's Law of ElectroMagnetic Induction. The Two Green dots in the animation indicates electrodes. The Copper co...

Electromagnetic Flow Meters Working Principle

Magnetic flow meter, simply known as mag flow meter is a volumetric flow meter which is ideally used for wastewater applications and other applications that experience low pressure drop and with app...

Control Valve Selection Guide

Control valves play a major role in the everyday effort to increase process plant profitability and conserve energy. Proper selection of these valves can have a significant financial impact on the o...

Comments

JOHN MULINDI:

This is a good explanation that is very helpful to students aspiring to pursue instrumentation at university or collage level.

بلال:

Thank you very much for the information

Anonymous:

is there any laser sensor[transmitter or switch ] and is it suitable for industrial use , if it is suitable what is the advantage and disadvantages comparing to ultrasonic or radar , thanks a lot for ...

Anonymous:

for controlling [start/stop] of pump which is the suitable ,radar or ultrasonic?
I am planning to use non contact switch

Instrumentation Android App

item