Closed tank DP Level Transmitter with wet leg elevation zero remote mount Calibration

The DP level transmitter installed below HP tapping point with wet leg.

Schematic Diagram of a Closed tank DP Level Transmitter with wet leg elevation zero remote mount Calibration

Closed tank DP Level Transmitter with wet leg elevation zero remote mount Calibration
Closed tank DP Level Transmitter with wet leg elevation zero remote mount Calibration

Formulas: 
Min range = (SG x X1) - (SG x H)
Max range = [(SGxX1) + (SGxX2)] - (SGxH)

You can use our instrumentation tools for easy & online calculation of transmitter ranges.CLICK HERE.

Example:

If the height is 1 meter an X1, X2 is 3 meters and a height H is 4.5 meters, in the tank there is cairin which has a density of 1 g / cm3, what is the range of calibration on the transmitter? 

SG = 1

Min range = P High - P Low
= (SG x X1) - (SG x H)
= (1 x 1) - (1 x 4.5) 
= 1 -4.5
= - 3.5 mH 2 O 

Max range = P High - P Low
= [(SGxX1) + (SGxX2)] - (SGxH)
= [(1x1) + (1x2) - (1x4,5)
= 4 to 4.5
= -0.5 MH 2 O

The transmitter Range = -3.5 to -0.5 mH 2 O 