Open Tank DP Level Transmitter Calibration
https://instrumentationtools.blogspot.com/2015/05/open-tank-dp-level-transmitter-calibration.html
Schematic Diagram of a open tank DP level transmitter installation
![]()  | 
| Open Tank DP Level Transmitter Calibration | 
Formulas: 
Min range = SG x h + P0 
Max range = SG x h + P 0
You can use our instrumentation tools for easy & online calculation of transmitter ranges.CLICK HERE.
Example:
If an X height is 10 meters and there is fluid in the tank which has a density of 0.85 g / cm3 what the calibration range of the transmitter? 
SG = 0.85
Min range = SG x h + P0 
= 0.85 x 0 m + 0 
= 0 mH 2 O 
Max range = SG x h + P 0 
= 0.85 x 10 m + 0 
= 8.5 mH 2 O
The transmitter calibration Range = 0 to 8.5 mH 2 O
Also Read:

