DP Level Transmitter with Zero Suppression Calibration

Schematic Diagram of a Open Tank DP Level Transmitter with Zero Suppression Calibration

Open Tank DP Level Transmitter with Zero Suppression Calibration

Formulas: 
Min range = SG x Z + P0 
Max range = (SG x Z) + (SG x H) 

You can use our instrumentation tools for easy & online calculation of transmitter ranges.CLICK HERE.

Example:

Note:
If the height of an H is 3.5 meters high and 1.5 meters Z is, in the tank there is a liquid that has a density of 1 g / cm3 what the calibration range of the transmitter? 

SG = 1

Min range = SG x Z + P0 
= 1 x 1,5 m + 0 
= 1.5 mH 2 O 

Max range = (SG x Z) + (SG x H) 
= (1 x 1.5) + (1 x 3.5) 
= 1.5 + 3.5 
= 5 mH2O 

The transmitter Range 1.5 to 5 mH2O 